Doing Inventory Control Right
For Underground Storage Tanks
Doing Inventory Control Right
State of New Jersey
Christine Todd Whitman
Governor
New Jersey Department of Environmental Protection
Robert C. Shinn, Jr.
Commissioner
August 1996
MAIL REQUESTS FOR COPIES TO:
New Jersey Department of Environmental Protection
Site Remediation Program
UST Brochure Request-Doing Inventory Control Right
CN 433
Trenton, New Jersey 08625
FOR MORE INFORMATION CALL: 609/292-8761
Why You Should Read This Booklet If You Use Inventory Control
Federal and state laws require underground storage tanks (USTs) to have leak detection.
Leak detection violations can keep you from getting legally required insurance coverage and reimbursement for cleanup Costs. Without leak detection, you constantly risk discovering a leak only after it becomes a major financial burden and an environmental problem. In addition, if your USTs do not have leak detection, you will not be in compliance with federal and state laws and may be subject to penalties.
If inventory control is part of your leak detection method, then this booklet can help you make sure you do inventory control correctly.
Inspections conducted nationwide indicate that most people who think they are doing inventory control are not doing it in a way that is likely to find leaks and meet the law's requirements for leak detection. So even if you are SURE you are doing inventory control right, read this booklet carefully–it could save you a lot of time and money.
If you need information on federal and state leak detection requirements and the various methods of leak detection available to you, see "Straight Talk On Tanks." Call DEP at 609/292-8761 and order this free publication by name.
How Does Inventory Control Work?
This booklet helps you use inventory control to meet federal and state regulatory leak detection requirements by showing you how to do three important tasks:
• Good sticking
• Good math
• Good recordkeeping
Without these three, your inventory control procedure will not meet leak detection requirements. To do inventory control right, you have to spend time to make sure that you consistently measure the tank's contents correctly, that you don't let math errors creep into your daily and monthly calculations, and that you keep complete, easy-to-read records on file for at least a year.
Basically, inventory control requires daily measurements of tank contents and math calculations that let you compare your "stick" inventory (what you've measured) to your "book" inventory (what your recordkeeping indicates you should have). Some people call this process "inventory reconciliation." If the difference between your "stick" and "book" inventories is too large, your tank may be leaking.
Be sure you read about several important restrictions on the use of inventory control that are described on the next page.
To use inventory control correctly,
follow Steps 1–5 starting on page 6.
Please note these important restrictions on the use of
inventory control as leak detection:
• Inventory control can never be used alone. Inventory control must always be used in combination with tank tightness testing. Tanks must be tightness tested every 12 months if they do not have corrosion protection and spill/overfill devices. Tanks with corrosion protection and spill/overfill devices must be tested every 5 years.
• Inventory control is a TEMPORARY leak detection method. You can use inventory control as leak detection on tanks that have NOT yet been upgraded with corrosion protection and spill/overfill devices (upgrade or tank closure must occur by December, 1998). You can continue to use inventory control as leak detection only for 10 years after upgrading an old tank with corrosion protection and spill/overfill devices. You can also use inventory control as leak detection for 10 years after installing a new tank that has corrosion protection and spill/overfill devices. After the 10-year period, you must use a monthly monitoring method, such as groundwater monitoring or interstitial monitoring.
• The combined use of inventory control and tank tightness testing does not meet your tank system's leak detection requirements for piping. Pressurized and some suction piping must use other methods of leak detection, such as interstitial monitoring. (See "Straight Talk On Tanks.")
Pay careful attention to these restrictions to meet the leak detection requirements.
Do You Have The Right Equipment?
Gauge Stick Or Other Gauges
The gauge stick used to measure the depth of liquid in an underground tank must be marked or notched to the _ inch, starting with zero at the bottom end. Check your stick to be sure the end has not been worn or cut off and that the stick is not warped. The stick should be made of non-sparking material, such as wood, and varnished to minimize the creeping of fuel above the actual fuel level in the tank. Instead of using a gauge stick, you may use a mechanical or electronic tank level monitor. Whatever measuring device you use must be capable of measuring the level of product over the full range of the tank's height to the nearest _ inch.
Pastes For Finding Water Or Fuel
You must check for water in the bottom of the tank at least once each month by smearing a water-finding paste along the bottom of the gauge stick. The paste changes color when it comes in contact with water. Many operators improve their stick readings by smearing a fuel-finding paste on about 6 inches of the stick where they expect the fuel level to be. Fuel-finding paste changes color when it comes in contact with fuel.
Forms
The instructions in this booklet are keyed to two forms: the "Daily Inventory Worksheet" and the "Monthly Inventory Record." You will find filled-in sample copies of these forms on the last two pages of this booklet. These samples are on perforated pages, so tear them out and refer to them while you read through the directions that are keyed alphabetically to the sample forms. Also, near the back of the booklet, you will find "masters" you can copy repeatedly to provide forms for use in your recordkeeping. If these forms are filled out according to the instructions in this booklet, you will be in compliance with federal and state regulations for inventory control. You can use other standard recordkeeping forms, as long as they are clear, consistent, and contain all the information required by the federal and state leak detection regulations.
Tank Chart
A tank chart is a table that converts the number of inches of liquid in the tank into the number of gallons. You need a tank chart that exactly matches your storage tank (tank manufacturers usually provide charts for their tanks). If you have more than one tank, you will need a chart for each tank unless the tanks are identical. The tank chart must show conversion to gallons for each _ inch stick reading. If your tank chart does not convert each _ inch reading into gallons, contact the tank manufacturer, or, if you have a steel tank, the Steel Tank Association (708 438-8265), to get an appropriate chart.
You always need to convert inches into gallons in order to fill out the forms correctly and to do the necessary math. To convert inches into gallons, find your stick's reading to the nearest _ inch on the tank chart, then simply read across to the gallons column to find the number of gallons. If you cannot get a tank chart showing conversion to gallons for each _ inch reading, you must do the additional math explained on page 9.
Drop Tube
The fill pipe through which the fuel is delivered into the tank must have a drop tube extending to within 1 foot of the bottom of the tank. Stick measurements should be made through a drop tube in the fill pipe or gauging port. If your fill pipe does not have a drop tube, call your petroleum equipment supplier to have one installed.
Calibrated Dispensing Meters
Meters must be calibrated according to local standards.
Manifolded Tanks
If you have manifolded tanks or dispensers that blend fuel, consider these tanks as one tank system if they share a common inventory of stored fuel. As you follow the directions on the following pages, you will need to combine your measurements and calculations for all the tanks manifolded into one system.
Step 1–Measure The Tank's Contents
You must measure the tank every day that fuel is added or removed. You may take measurements using a gauge stick or a mechanical or electronic tank level monitor.
No fuel can be added or removed from the tank while you are performing Step 1 or Step 2.
Every day you measure the tank, you should fill out a "daily inventory worksheet." As you go through the following directions, refer to the sample daily inventory worksheet you will find toward the end of this booklet. For easy reference, the sample is on a perforated page so you can tear it out and keep it handy as you read through the directions. Also, near the back of the booklet is a "master copy" on a perforated page you can tear out to make copies of the daily inventory worksheet for your recordkeeping.
10 Fill in the identifying information at the top of the worksheet.
11 Next to the "Tank Identification" box are empty vertical columns. Each column represents one tank—consistently enter all information on that one tank in the same vertical column. NOTE: Once you have filled in the tank identification boxes, make copies of the worksheet so you won't have to repeatedly enter the same information.
USE GOOD STICKING PRACTICES: Slowly lower the gauge stick to the tank's bottom. Let the stick gently touch the bottom, then quickly bring it back up. Read the depth of fuel indicated by the wet mark to the closest _ inch division on the stick. Use of fuel-finding paste will make your stick readings more accurate.
13 Write your measurement in the box labeled "End Stick Inches" for the tank you measured.
NOTE: If your tank is equipped with an automatic tank gauge (ATG), you may record the inches of product and gallons of product directly from the ATG's printed tape or simply staple the tape with this information to the worksheet.
Step 2–Record The Amount Pumped
At the same time you measure the tank contents (Step 1), you must record on the daily inventory worksheet the amount of fuel pumped. No fuel can be added or removed from the tank while you are sticking the tank and recording the amount pumped.
15Locate the box labeled "Amount Pumped" on the left side of the worksheet. Copy the numbers from each dispenser's totalizer onto the worksheet. Be very careful that you write all the meter readings for a tank in the same column. You may have several dispensers and totalizers for one tank, so the worksheet provides boxes in which you can enter several readings in any order.
16Add up the totalizer meter readings in each column and write the result in the box labeled "Today's Sum of Totalizers."
17Find the last daily inventory worksheet you completed. Copy "Today's Sum of Totalizers" from that worksheet into the "Previous Day's Sum of Totalizers" box of the worksheet you are working on today.
18On today's worksheet, subtract "Previous Day's Sum of Totalizers" from "Today's Sum of Totalizers" and write the result in the box labeled "Amount Pumped Today."
19If you are using cash register reports to record the amount pumped, enter the amount of each type of fuel pumped in the box labeled "Amount Pumped Today" or staple the printout to the worksheet.
Step 3–Record Fuel Deliveries
You must check how much fuel has been delivered every time any amount of fuel is delivered to your tank. NOTE: You should not pump any fuel during the time it takes to do items "I" and "J" below.
Before the delivery begins, the liquid level in the tank must be measured. Always use good sticking practices: slowly lower the gauge stick, gently touch the stick to the bottom of the tank, then quickly bring the stick back up. Read the depth of fuel indicated by the wet mark to the nearest _ inch division on the stick.
21 Write your measurement in the box labeled "Inches of Fuel Before Delivery" for each tank you measured.
The delivery person can now deliver fuel into the tank. After the delivery, wait at least 5 minutes for the fuel level in the tank to stabilize, and then measure again as described above.
22 Record fuel level in the box labeled "Inches of Fuel After Delivery."
23 Using your tank chart with _ inch readings, convert both delivery readings to the correct number of gallons. Record these numbers in the boxes labeled "Gallons of Fuel Before Delivery" and "Gallons of Fuel After Delivery." (If necessary, see page 9 on converting inches into gallons.)
24 Subtract "Gallons of Fuel Before Delivery" from "Gallons of Fuel After Delivery." Record the result in the box labeled "Gallons Delivered (Stick)."
Now look at the delivery receipt and find the volume of each type of product that was delivered. If two volumes are given, one labeled "net" and the other "gross," use the gross gallons as the volume of product delivered.
25 For each type of fuel delivered, copy the gross gallons delivered from the delivery receipt onto the worksheet in the box labeled "Gross Gallons Delivered (Receipt)." The gallons in items "L" and "M" should roughly match. If they don't, contact your supplier.
Using Tank Charts Without _ Inch Conversions
If your tank chart does not list direct conversions from inches to gallons for every _ inch, then you must do the additional math described below every time you stick your tank.
The easiest way to explain this procedure is with an example. Let's say you have a stick reading of 43_ inches and you need to figure how many gallons are in your tank.
1.Look on your tank chart and find the inch measurements that are just above and below your stick reading and write down the number of gallons for these inch readings. Subtract the gallon readings to find the difference between the two readings:
Chart reading at 44 inches: 3,585 gallons
Chart reading at 43 inches: 3,480 gallons
-----------------------------------------------------------------------------------
Difference: 105 gallons
2.Dividing 105 by 8 will give you the number of gallons per _ inch, which in this example is 13. (More exactly it is 13.125, but do round off the number to the nearest whole number.) Because your fraction is _, multiply 13 gallons by 3, which gives you 39 gallons as the volume represented by _ inch.
CAUTION: The gallons represented by each _ inch will vary from top to bottom of the tank and must be calculated for each conversion.
3.Take the number of gallons you have just calculated and add it to the inch reading just below your actual stick reading:
Chart reading at 43 inches: 3,480 gallons
Gallons at _ inch: + 39 gallons
-----------------------------------------------------------------------------------
Sum: 3,519 gallons
Thus, your stick reading of 43_ inches converts to 3,519 gallons.
NOTE: If your tank chart is in half or quarter inches, you must still use this procedure so that your gallon readings are accurate to _ inch.
After all of this math, you can see why it pays to have the correct tank chart that indicates gallons for each _ inch.
Step 4–Calculate Daily Changes In Inventory
In this step, you will copy information from the daily inventory worksheet onto the monthly inventory record. You will then do some math to determine your daily inventory. You need one monthly inventory record for each tank that you have.
As you go through the following directions, refer to the sample monthly inventory record you will find on the reverse side of the daily inventory worksheet sample you have already been using. For easy reference, the sample is on a perforated page so you can tear it out and keep it handy as you read through the directions. Also, near the back of the booklet is a "master copy" on a perforated page you can tear out to make copies of the monthly inventory record for your recordkeeping.
27 Fill in the identifying information at the top of the monthly inventory record.
If this is the very first day of your inventory recordkeeping, convert the "End Stick Inches" from the daily worksheet into gallons and enter on the monthly record under "End Stick Inventory (Gallons)" for that starting date. (If necessary, see page 9 on converting inches into gallons.) This is all you can do today. Starting tomorrow, follow all of the instructions listed below.
28 Find the line in the left column on the monthly record with today's date listed. Copy the previous day's "End Stick Inventory (Gallons)" number into the box for today's "Start Stick Inventory (Gallons)."
29 Enter the amount of fuel delivered from the daily inventory worksheet. If you were NOT pumping fuel during the time when the delivery was taking place, then use the "Gallons Delivered (Stick)" number. However, if you had to pump fuel while the delivery was taking place, then use the "Gross Gallons Delivered (Receipt)" number as your delivery amount.
30 Copy the "Amount Pumped Today" number from the daily inventory worksheet into the "Gallons Pumped" column of the monthly inventory record.
31 Add the "Start Stick Inventory (Gallons)" and the "Gallons Delivered" columns; then subtract the "Gallons Pumped" column. Enter the result in the column labeled "Book Inventory (Gallons)."
32 Copy the "End Stick Inches" number from the daily worksheet into the column labeled "End Stick Inventory (Inches)" on the monthly record. Convert inches into gallons and enter the result in the column on the monthly record labeled "End Stick Inventory (Gallons)." (If necessary, see page 9 on converting inches into gallons.)
33 Subtract the "Book Inventory (Gallons)" from the "End Stick Inventory (Gallons)." Enter the difference into today's "Daily Over or Short" box. This number will usually be a positive or negative number (only rarely will it be zero).
34 Enter your initials to show who entered today's information.
At least once each month, you must also measure for water in the tank. Smear water-finding paste on the bottom few inches of the gauge stick. Open the fill pipe and slowly lower the stick to the tank's bottom. Hold the stick on the bottom for 10 seconds for gasoline (30 seconds for diesel). Then remove the stick. If there is water in the bottom of the tank, the water-finding paste will change color. Read the depth of water indicated by the line where the water-finding paste has changed color to the closest _ inch division on the stick. Do not use this stick reading to measure the amount of fuel in the tank, because the fuel will creep up the stick and will give you an inaccurate reading.
36 If you checked the tank for water today, enter the number of inches of water in the tank on the line under "Facility Name" at the top of the monthly record. If there is no water present, enter a zero to indicate that you in fact checked for water but found none. If you find more than 1 inch of water, you should arrange for its immediate removal, notify the product supplier, and conduct further tests to ensure that the tank is not leaking.
Step 5–Calculate Monthly Changes In Inventory
At the end of each month, follow the directions below to see if the difference between "stick" and "book" inventory indicates a possible leak.
38 Add all of the month's "Gallons Pumped" numbers and write this total at the bottom of the column in the box labeled "Total Gallons Pumped."
39 Add all the month's "Daily Over or Short" numbers: pay careful attention to positive and negative numbers to get an accurate total. For example, adding +4 and +3 and -2 should equal +5. Enter the total at the bottom of the column in the box labeled "Total Gallons Over or Short."
40 Fill out the "Leak Check" line at the bottom of the monthly inventory record as follows:
• Take the "Total Gallons Pumped" number and drop the last two digits to get 1% (for example: 6594 becomes 65).
• Add 130 (for example: 65 + 130 = 195).
Enter the result of this calculation at the end of the "Leak Check" line. This number is the maximum change in inventory allowed by federal regulations (1% of throughput plus 130 gallons).
41 At the bottom of the monthly inventory record, circle "YES" or "NO" to show whether your "Total Gallons Over or Short" number is LARGER than the "leak check" number you identified in the previous item. Even if your "Total Gallons Over or Short" is a negative number, treat it as a positive number for the purpose of this comparison. For example, -74 would become +74.
If you circle YES, you have a "suspected release". You then have seven days to conduct an investigation to confirm or disprove that your tank is leaking. Once your investigation has been completed, if you have confirmed that your tank is leaking, then you must notify DEP immediately by calling the Environmental Action Hotline (609 292-7172). After calling, you must arrange to clean up the contamination from your leak. To perform a proper cleanup (also called "corrective action"), you must follow the Technical Requirements for Site Remediation (N.J.A.C. 7:26E). Copies of N.J.A.C. 7:26E can be ordered from the Office of Administrative Law at 609 588-6606. Within 120 days of reporting your leak, you must also submit a remedial investigation report to the DEP, describing all cleanup activities conducted and results found.
DAILY INVENTORY WORKSHEET
FACILITY NAME: _________________________________________
YOUR NAME: _________________________________________
DATE: _________________________________________
TANK IDENTIFICATION |
|||||
Type of Fuel |
|||||
Tank Size in Gallons |
|||||
END STICK INCHES |
|||||
AMOUNT PUMPED |
¯ |
¯ |
¯ |
¯ |
¯ |
Totalizer Reading |
|||||
Totalizer Reading |
|||||
Totalizer Reading |
|||||
Totalizer Reading |
|||||
Totalizer Reading |
|||||
Totalizer Reading |
|||||
Totalizer Reading |
|||||
Totalizer Reading |
|||||
TODAY'S SUM OF TOTALIZERS |
|||||
Previous Day's Sum of Totalizers |
|||||
AMOUNT PUMPED TODAY |
|||||
DELIVERY RECORD |
¯ |
¯ |
¯ |
¯ |
¯ |
Inches of Fuel Before Delivery |
|||||
Gallons of Fuel Before Delivery (from tank chart) |
|||||
Inches of Fuel After Delivery |
|||||
Gallons of Fuel After Delivery (from tank chart) |
|||||
GALLONS DELIVERED (STICK) [Gallons "After" - Gallons "Before"] |
|||||
GROSS GALLONS DELIVERED (RECEIPT) |
MONTHLY INVENTORY RECORD
TANK IDENTIFICATION & TYPE OF FUEL: ____________________________________
MONTH/YEAR :_______/______
FACILITY NAME: ___________________________________________________________
DATE OF WATER CHECK: ___________ LEVEL OF WATER (INCHES):_________
DATE |
START STICK INVENTORY (GALLONS) |
GALLONS DELIVERED |
GALLONS PUMPED |
BOOK INVENTORY (GALLONS) |
END STICK INVENTORY ____________________________ (INCHES) % (GALLONS) |
DAILY OVER (+) OR SHORT (-) ["End" - "Book"] |
INITIALS |
|
1 |
(+) (-) (=) |
|||||||
2 |
(+) (-) (=) |
|||||||
3 |
(+) (-) (=) |
|||||||
4 |
(+) (-) (=) |
|||||||
5 |
(+) (-) (=) |
|||||||
6 |
(+) (-) (=) |
|||||||
7 |
(+) (-) (=) |
|||||||
8 |
(+) (-) (=) |
|||||||
9 |
(+) (-) (=) |
|||||||
10 |
(+) (-) (=) |
|||||||
11 |
(+) (-) (=) |
|||||||
12 |
(+) (-) (=) |
|||||||
13 |
(+) (-) (=) |
|||||||
14 |
(+) (-) (=) |
|||||||
15 |
(+) (-) (=) |
|||||||
16 |
(+) (-) (=) |
|||||||
17 |
(+) (-) (=) |
|||||||
18 |
(+) (-) (=) |
|||||||
19 |
(+) (-) (=) |
|||||||
20 |
(+) (-) (=) |
|||||||
21 |
(+) (-) (=) |
|||||||
22 |
(+) (-) (=) |
|||||||
23 |
(+) (-) (=) |
|||||||
24 |
(+) (-) (=) |
|||||||
25 |
(+) (-) (=) |
|||||||
26 |
(+) (-) (=) |
|||||||
27 |
(+) (-) (=) |
|||||||
28 |
(+) (-) (=) |
|||||||
29 |
(+) (-) (=) |
|||||||
30 |
(+) (-) (=) |
|||||||
31 |
(+) (-) (=) |
|||||||
TOTAL GALLONS PUMPED > |
TOTAL GALLONS OVER OR SHORT > |
DROP THE LAST 2 DIGITS from the TOTAL GALLONS
PUMPED number and enter on the line below Compare these numbers
LEAK CHECK: _____________ + 130 = ____________ gallons
Is "TOTAL GALLONS OVER OR SHORT" LARGER than "LEAK CHECK" result? YES NO (circle one)
If answer is "YES", investigate for a suspected release (see page 12).
KEEP THIS PIECE OF PAPER ON FILE
>>>Copy and post this reminder where employees
who measure tanks can see it!<<<
GET GOOD INVENTORY CONTROL MEASUREMENTS! • Measure each tank every operating day • Use gauge sticks that are _ marked to the _ inch _ not cut off or worn off at the "0" end _ varnished and not warped • Measure through the same drop tube each time • Use good sticking practices _ SLOWLY lower stick _ GENTLY touch stick on tank bottom _ QUICKLY pull stick out • Measure just before each delivery • Wait at least 5 minutes after delivery, then measure again • Read and record totalizer meters carefully • Check for water at least once a month using water-finding paste
|